Battery peak-shaving sizer

A battery that discharges during the demand peak lets the site draw fewer kVA from the grid. This sizer works out the inverter kW and battery kWh to hold demand at a target, and what that is worth.

Inputs

Pre-filled with an illustrative case. Results update as you type. Jump to results

Demand peak
kVA
kVA
hours
per year

250 is about every working day.

Tariff
R/kVA/month
c/kWh
c/kWh
Battery
R/kWh

Per nameplate kWh, inverter included.

R/kW

0 if included per kWh.

Battery performance
Battery performance
%
%
%

The battery is sized to still do the job then.

%
cycles
years

Results

175 kW inverter and 354 kWh battery cut demand by 150 kVA, worth about R134k a year; payback 15.9 years.

Inverter power
175kW
159 kW to shave + 10%
Battery energy
354kWh
Nameplate; 239 kWh delivered per event
Annual value
R134k
Cost R2.1m
Simple payback
15.9years
Expected life 15 years

NoteThe battery supplies real power only, so cutting 150 kVA needs 159 kW, not the 143 kW a kVA × power factor shortcut suggests. Correcting the power factor first makes the battery smaller.

RiskThe battery does not pay for itself within its expected life on these numbers. Peak shaving alone rarely does; stacking other value (backup, solar shifting, TOU arbitrage) usually decides the case.

Where the value comes from

Rand a year.

R0R20kR40kR60kR80kR100kDemand charges: R108kDemand chargesR108kEnergy shifting: R26kEnergy shiftingR26k

Sizing

Peak shape factor 0.75: the share of a flat block of energy the peak contains.

MeasureValue
Real power at the peak950 kW
Reactive power (unchanged)312 kvar
Real power allowed at the target791 kW
Battery power to shave159 kW
Energy delivered per event (AC)239 kWh
Energy drawn from the cells (DC)255 kWh
Nameplate energy354 kWh
Power-to-energy ratio (C-rate)0.50 C
Equivalent full cycles a year200
Expected life15.0 years
Net value over life (undiscounted)−R115,128

Add to a business case

What is this?

Save this result as one measure in a project kept in this browser, then combine it with results from other tools for payback, NPV, IRR and a cost curve.

Saving, year 1
R133,953/yrAssumed
Energy added
8,153 kWh/yrAssumed
Demand reduced
150 kVACalculated
Capex
R2,124,420Assumed
Life
15 yearsAssumed

Every input above is still the illustrative example, so the result is tagged assumed. Enter your own numbers to make it yours.

Assumed
R/yr

Maintenance, monitoring and insurance. Default: 1% of capex a year.

Method

Real and reactive power at the peak
P₁ = S₁ × pf, Q = S₁ × √(1 − pf²)
Battery power to reach the target
P₂ = √(S₂² − Q²), P_batt = P₁ − P₂
Reactive power is unchanged, so the target must be above Q.
Energy per event
E_ac = P_batt × hours × shape factor (flat 1, ramped 0.75, spike 0.5)
Nameplate energy
E_dc = E_ac ÷ √RTE, nameplate = E_dc ÷ (DoD × end-of-life capacity)
Life
cycles = events × E_dc ÷ (nameplate × DoD), life = min(calendar life, cycle life ÷ cycles)
Annual value
(S₁ − S₂) × R/kVA × 12 + events × (E_ac × c_discharge − E_ac ÷ RTE × c_charge) ÷ 100
Cost and payback
capex = nameplate × R/kWh + inverter kW × R/kW, payback = capex ÷ annual value

Assumptions

  • Every month has a similar peak, and the battery shaves it every month: the demand saving is counted 12 times a year.
  • The battery is fully recharged between events, off-peak, and is sized so it still covers the event at the end-of-life capacity.
  • Discharge efficiency is the square root of round-trip efficiency (losses split evenly between charging and discharging).
  • No degradation of the value over time, no discounting, no replacement, maintenance or insurance costs; the payback is simple.
  • Default costs, efficiency (88%) and cycle life (6,000) are illustrative for a lithium iron phosphate system.

Sources

More technical tools

All technical tools
  • Technical

    Notified maximum demand (NMD) optimiser

    From 12 months of maximum demand, recommend an NMD with headroom, estimate the capacity-charge saving and flag the risk of exceedance charges.

    You need
    12 monthly maximum demands (kVA), current NMD, capacity charges (R/kVA)
    You get
    Recommended NMD, annual saving, exceedance risk, cost curve
    Open the tool
  • Technical

    Power-factor correction sizing

    Size a capacitor bank from kW and power factor, and see the kVA reduction, demand-charge saving and payback.

    You need
    kW at maximum demand, power factor now and target, R/kVA demand charge
    You get
    kvar required, bank size, kVA and current reduction, saving, payback
    Open the tool
  • Technical

    Load factor and time-of-use profile analyser

    From kWh by time-of-use period and the maximum demand, find the load factor, peak share, all-in cost per kWh and the value of shifting load out of peak.

    You need
    Peak, standard and off-peak kWh, maximum demand, c/kWh rates
    You get
    Load factor, TOU split, c/kWh, saving from load shifting
    Open the tool

Also for finance, commercial and investment people: Business case, Solar PPA project finance and more.